Exergy analysis of heat pumps for simultaneous heating and cooling

•Two prototypes of heat pump for simultaneous heating and cooling were built and tested.•An exergy analysis was performed to assess the operation of each component.•Design problems were detected and improvements were made between 1st and 2nd prototypes.•Exergy destruction should be low and balanced...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Applied thermal engineering 2019-02, Vol.149, p.414-424
Hauptverfasser: Byrne, Paul, Ghoubali, Redouane
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:•Two prototypes of heat pump for simultaneous heating and cooling were built and tested.•An exergy analysis was performed to assess the operation of each component.•Design problems were detected and improvements were made between 1st and 2nd prototypes.•Exergy destruction should be low and balanced between components. This article presents the evolution of a concept of air-source heat pump for simultaneous heating and cooling (HPS). A heat pump can simultaneously produce heating and cooling energies for collective residential buildings, hotels or highly-glazed office buildings. The heat pump prototypes operate under three main modes. (1) The heating mode produces hot water using heat available in the ambient air. (2) The cooling mode produces cold water and rejects heat to the ambient air. (3) The simultaneous mode produces hot water thanks to heat taken from the cold water, therefore becoming colder. During the simultaneous mode, two thermal energy amounts, for cooling and heating, are produced simultaneously. Therefore, it is interesting for the user that the heat pump operates in the simultaneous mode as much as possible. A winter operating sequence involving a heat exchanger for refrigerant subcooling enhances the performance of the machine. Two prototypes working with R407C and R290 (propane) were built consecutively and tested following European Standard EN 14,511 in a climatic chamber. The experimental results show that the second prototype has a higher performance than the first one regarding exergy aspects thanks to not only the refrigerant choice but also to a better design of components.
ISSN:1359-4311