Evaluation of Shelter Ventilation by Model Tests, Option 1 - Below Ground Shelters

Wind-induced ventilation rates that could be achieved in a 100-man below-ground shelter with simple designs of passive flow enhancement devices (FEDs) were estimated by scale model tests in a low-speed wind tunnel. Air volume flow rates through the model were determined by using bubble flow tracers...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Hauptverfasser: Krishnakumar, C K, Koh, J B, Fields, S F, Henninger, R H
Format: Report
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Wind-induced ventilation rates that could be achieved in a 100-man below-ground shelter with simple designs of passive flow enhancement devices (FEDs) were estimated by scale model tests in a low-speed wind tunnel. Air volume flow rates through the model were determined by using bubble flow tracers and motion photography. Test results indicate that adequate ventilation can be achieved in the type of shelter considered by the use of FEDs even at relatively low wind speeds. The study also generated guidelines for the relatively low speeds. The study also generated guidelines for the design of FEDs and their placement around stairway openings. In addition, estimates of reductions in ventilation rates due to an obstruction upstream of the windward FED and due to a decrease in the area of wall openings were made. Update to report dated Mar 83, AD-A126 765. Includes summary dated Sep 1983.