Current Sensorless Pole-Zero Cancellation Output Voltage Control for Uninterruptible Power Supply Systems with a Three-Phase Inverter

This article presents a proportional–derivative (PD) type output voltage regulator without the current feedback, taking into account system parameter and load variations. The main advantages are given as follows: First, the first-order output voltage derivative observer is developed without the requ...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Energies (Basel) 2024-04, Vol.17 (7), p.1738
Hauptverfasser: Lee, Hosik, Kim, Yonghun, Kim, Seok-Kyoon
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This article presents a proportional–derivative (PD) type output voltage regulator without the current feedback, taking into account system parameter and load variations. The main advantages are given as follows: First, the first-order output voltage derivative observer is developed without the requirement of system parameter information, which makes it possible to stabilize the system without current sensing. Second, a simple self-tuner implements the feedback-loop adaptation by updating the desired dynamics accordingly. Third, the observer-based active damping injection for the PD-type controller results in the closed-loop system order reduction to 1 by the pole-zero cancellation, including the disturbance observer as a feed-forward term. The prototype uninterruptible power supply system comprised of a 3 kW three-phase inverter, inductors, and capacitors verifies the practical merits of the proposed technique for linear and nonlinear loads.
ISSN:1996-1073
1996-1073