Effectiveness of Distributed vs. Concentrated Volt/Var Local Control Strategies in Low-Voltage Grids

This paper introduces a novel local Volt/var control strategy in a low-voltage smart grid. Nowadays, various Volt/var local control strategies built on customer photovoltaic inverters, e.g., cosφ(P) and Q(U), are introduced to mitigate the upper voltage limit violations in feeders with high prosumer...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Applied sciences 2018-08, Vol.8 (8), p.1382
Hauptverfasser: Ilo, Albana, Schultis, Daniel-Leon, Schirmer, Christian
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This paper introduces a novel local Volt/var control strategy in a low-voltage smart grid. Nowadays, various Volt/var local control strategies built on customer photovoltaic inverters, e.g., cosφ(P) and Q(U), are introduced to mitigate the upper voltage limit violations in feeders with high prosumer share. Nevertheless, although these strategies are further refined by including more local variables, their use is still very limited. In this study, the effects of a new concentrated Volt/var local control strategy in low-voltage grids are investigated. Concentrated var-sinks, e.g., coils-L(U), are set at the end of each violated feeder. The concentrated local control strategy L(U) is compared with the distributed cosφ(P) and Q(U) strategies. Initially, both control strategies are theoretically investigated, followed by simulations in a test feeder. Finally, the expected practical significance of the findings is verified through simulations in a real typical urban and rural grid. Additionally, the impact of the different local control strategies used in low-voltage grids on the behavior of the medium-voltage grid is analyzed. The results show that the concentrated Volt/var control strategy eliminates the violation of upper voltage limit even in longer feeders, where both distributed local strategies fail. In addition, the concentrated L(U) local control causes less reactive power exchange on the distribution transformer level than the distributed cosφ(P) and Q(U) strategies. Therefore, the reactive power exchange with the medium-voltage grid and thus the distribution transformer loading are smaller in the case of concentrated local control strategy.
ISSN:2076-3417
2076-3417
DOI:10.3390/app8081382