A Study on Frequency Stability and Primary Frequency Response of the Korean Electric Power System Considering the High Penetration of Wind Power
The high penetration of wind power decreases the system inertia and primary frequency reserve while replacing the conventional synchronous generators (SGs). Therefore, if the system operator does not take appropriate action on the remaining generation units (GUs) operation, high penetration of wind...
Gespeichert in:
Veröffentlicht in: | Energies (Basel) 2022-03, Vol.15 (5), p.1784 |
---|---|
Hauptverfasser: | , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The high penetration of wind power decreases the system inertia and primary frequency reserve while replacing the conventional synchronous generators (SGs). Therefore, if the system operator does not take appropriate action on the remaining generation units (GUs) operation, high penetration of wind power will aggravate the frequency stability. To solve this problem, wind power plants (WPPs) may provide the inertial response and primary frequency response (PFR) to support the frequency stability. However, due to the variability of renewable energy, WPPs may not provide adequate frequency response whenever it is required. This paper proposes an algorithm to determine the operation of GUs to provide appropriate PFR for a power system with high penetration of wind power. Through the proposed algorithm, it calculates the required PFR to restore the decreased frequency stability caused by the high penetration of wind power. Then, while considering the available PFR from WPPs, it redetermines the droop coefficient of SGs governor to provide the sufficient PFR to recover the frequency stability. Finally, the effectiveness of the proposed algorithm is verified on the practical Korean electric power system. |
---|---|
ISSN: | 1996-1073 1996-1073 |
DOI: | 10.3390/en15051784 |