Additional electric loss in rural distribution networks 0.38 kV

The article presents calculations the additional electric loss in the case of three-phase voltage system unbalance in the real rural electrical distribution networks (0.38 kV). Measurements were carried out at substations that receive power from distribution substation “Petropavlovsk”. Measurements...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:E3S web of conferences 2020-01, Vol.209, p.7007
Hauptverfasser: Naumov, Igor, Karamov, Dmitriy, Tretyakov, Alexander, Fedorinova, Elvira, Yakupova, Marina
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The article presents calculations the additional electric loss in the case of three-phase voltage system unbalance in the real rural electrical distribution networks (0.38 kV). Measurements were carried out at substations that receive power from distribution substation “Petropavlovsk”. Measurements were carried out using a certified device “Resource-UF2M”. Also presented are graphs of changes in currents/voltages of the negative-sequence and zero-sequence, electric loss and other parameters. The results of the economic assessment of electricity losses are presented. As a result, the proposed method for reducing the power loss factor, that can reduce the losses of electricity.