Evaluation of Annual Performance of Multi-type Air-conditioners for Buildings
The partial thermal load performance tests of electric-motor driven multi-type air-conditioners for buildings, the rated cooling and heating capacities of which were 56 kW and 63 kW, respectively, were carried out using the air-enthalpy method testing apparatus. Based on the results of those tests,...
Gespeichert in:
Veröffentlicht in: | Journal of Thermal Science and Technology 2009, Vol.4(4), pp.483-493 |
---|---|
Hauptverfasser: | , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The partial thermal load performance tests of electric-motor driven multi-type air-conditioners for buildings, the rated cooling and heating capacities of which were 56 kW and 63 kW, respectively, were carried out using the air-enthalpy method testing apparatus. Based on the results of those tests, the applicability of JIS B 8616: 2006, which was developed for the estimation of the annual electricity consumption of packaged air-conditioners with rated cooling capacities less than 28 kW, to the multi-type air-conditioners with larger capacities were examined. It was found that JIS B 8616: 2006 generally overestimates COP under a relatively low thermal load operation. As a result, the annual electricity consumption is underestimated by JIS. The prediction error changes depending of the building uses, and it amounted to -17 % in the case of office and -6 % in the detached shop. |
---|---|