The features of the dielectric rod defects and the rod-electrod defects of polymer insulators were investigated by using the developed complex method of contactless remote diagnostics of high-voltage insulators health, which includes the initial detection of local areas with elevated electric field...
Gespeichert in:
Veröffentlicht in: | E3S web of conferences 2019-01, Vol.124, p.1039 |
---|---|
Hauptverfasser: | , , |
Format: | Artikel |
Sprache: | eng |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The features of the dielectric rod defects and the rod-electrod defects of polymer insulators were investigated by using the developed complex method of contactless remote diagnostics of high-voltage insulators health, which includes the initial detection of local areas with elevated electric field gradients as well as measurement of a set of partial discharges characteristics. The radiation of extra-large partial discharges was detected and partial discharges features were investigated. According to the measurement results, a diagram was constructed for the electro-physical processes that accompany the emission of extra-large partial discharges; and the reasons for their occurrence were established. |
---|---|
ISSN: | 2267-1242 2267-1242 |
DOI: | 10.1051/e3sconf/201912401039 |