Space cooling using geothermal single‐effect water/lithium bromide absorption chiller
This research is proposed to fully investigate the performance of a single‐effect water/lithium bromide absorption chiller driven by geothermal energy. Since absorption cycles are considered as low‐grade energy cycles, this innovative idea of rejecting fluid from a single‐flash geothermal power plan...
Gespeichert in:
Veröffentlicht in: | Energy science & engineering 2021-10, Vol.9 (10), p.1747-1760 |
---|---|
Hauptverfasser: | , , , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | This research is proposed to fully investigate the performance of a single‐effect water/lithium bromide absorption chiller driven by geothermal energy. Since absorption cycles are considered as low‐grade energy cycles, this innovative idea of rejecting fluid from a single‐flash geothermal power plant with low‐grade energy would serve as efficient, economical, and promising technology. In order to examine the feasibility of this approach, a residential building which is located in Sharjah, UAE, considered to evaluate its cooling capacity of 39 kW which is calculated using MATLAB software. Based on the obtained cooling load, modeling of the required water/lithium bromide single‐effect absorption chiller machine is implemented and discussed. A detailed performance analysis of the proposed model under different conditions is performed using Engineering Equation Solver software (EES). Based on the obtained results, the major factors in the design of the proposed system are the size of the heat exchangers and the input heat source temperature. The results are presented graphically to find out the geofluid temperature and mass flow and solution heat exchanger effectiveness effects on the chiller thermal performance. Moreover, the effects of the size of all components of the absorption chiller on the cooling load to meet the space heating are presented. The thermal efficiency of the single‐flash geothermal power plant is about 13% when the power plant is at production well temperature 250℃, separator pressure 0.24 MPa, and condenser pressure 7.5 kPa. The results show that the coefficient of performance (COP) reaches about 0.87 at solution heat exchanger effectiveness of 0.9, when the geofluid temperature is 120℃.
1. Performance analysis of geothermal water/lithium bromide absorption chiller is presented. 2. Cooling load of the absorption chiller was determined for a residential building. 3. MATLAB and EES software are used in the analysis. 4. Size of heat exchangers and heat source inlet temperature are the most effective parameters on performance. 5. Graphical diagrams are presented for the results. |
---|---|
ISSN: | 2050-0505 2050-0505 |
DOI: | 10.1002/ese3.946 |