Mutual Coupling Compensation Techniques Used for Distance Protection of Parallel Lines

When a distance relay protects a transmission line located on a dual circuit tower, a coupling effect will occur between the two circuits. Transposition of the circuits can reduce the mutual impedances, but this does not cater to the zero-sequence mutual coupling impedance during earth faults. As a...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Energies (Basel) 2021-04, Vol.14 (7), p.1982
Hauptverfasser: O Donovan, Michael, Barry, Noel, Connell, Joe, Cowhey, Eoin
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:When a distance relay protects a transmission line located on a dual circuit tower, a coupling effect will occur between the two circuits. Transposition of the circuits can reduce the mutual impedances, but this does not cater to the zero-sequence mutual coupling impedance during earth faults. As a result, the impedance measured by a distance relay under phase-to-earth fault conditions in these circumstances will not represent the correct impedance to the fault point unless these effects are taken into account. On multi-circuit lines, primarily if they operate in parallel, a zero-sequence mutual coupling should be considered when calculating settings for distance protection function. A 220 kV parallel line sharing the same tower was analysed using DigSilent Power Factory in the simulations. Phase-to-earth faults in different configurations were analysed on this system, and the reach of the protection relay was then estimated for operation. The results confirm how a protection relay can overreach and underreach in a distance protection scheme due to the influence of mutual coupling.
ISSN:1996-1073
1996-1073
DOI:10.3390/en14071982