Magnetic Sensor Array for Electric Arc Reconstruction in Circuit Breakers

Noninvasive imaging of circuit breakers under short-circuit testing is addressed by recording the magnetic field produced over an array of external sensors and by solving an inverse problem to identify the causing current distribution. The temporal and spatial resolution of the sensing chain are stu...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Sensors (Basel, Switzerland) Switzerland), 2024-09, Vol.24 (17), p.5779
Hauptverfasser: D'Antona, Gabriele, Ghezzi, Luca, Prando, Sara, Rigamonti, Francesco
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Noninvasive imaging of circuit breakers under short-circuit testing is addressed by recording the magnetic field produced over an array of external sensors and by solving an inverse problem to identify the causing current distribution. The temporal and spatial resolution of the sensing chain are studied and implemented in a physical set-up. A wire model is adopted to describe electrical current distribution. Additionally, the simpler, more direct approach to evaluating the passage of electric current in front of sensors is proposed. The dynamics of suitable approximating models of the electric arc that forms across contacts is obtained and agrees with multi-physical simulations and with experimental time histories of current and voltage. The two methods are flexible and allow the analysis of different types of circuit breakers.
ISSN:1424-8220
1424-8220
DOI:10.3390/s24175779