Modeling and Enhanced Error-Free Current Control Strategy for Inverter with Virtual Resistor Damping

In microgrid, the grid-connected inverter current with the LCL (inductor-capacitor-inductor) output filter is amplified at certain frequencies. Using virtual resistor damping method can help suppress the amplification. By choosing an appropriate virtual resistor value, the model of the inverter curr...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Energies (Basel) 2018-10, Vol.11 (10), p.2499
Hauptverfasser: Nie, Cheng, Wang, Yue, Lei, Wanjun, Li, Tian, Yin, Shiyuan
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:In microgrid, the grid-connected inverter current with the LCL (inductor-capacitor-inductor) output filter is amplified at certain frequencies. Using virtual resistor damping method can help suppress the amplification. By choosing an appropriate virtual resistor value, the model of the inverter current control loop is simplified as a 2nd-order lowpass filter. Based on such simplified model, this paper proposes a design method of reference current compensation controller, which does not require decomposition of harmonic components. With the reference compensation, the inverter output current control precision is improved obviously. The simulation and experimental results verify the accuracy of the inverter simplified model and effectiveness of the reference compensation design method.
ISSN:1996-1073
1996-1073
DOI:10.3390/en11102499