Effect of benzotriazole on the existing pits of copper tube in fire sprinkler system
In this paper, two leaking tubes were investigated among copper tubes injected with 200 and 400 ppm benzotriazole after 8 years of usage. The electrochemical tests were conducted in simulated pit-out and pit-in environments (i.e., regions outside and inside of the pit) to determine the effect of ben...
Gespeichert in:
Veröffentlicht in: | Heliyon 2023-12, Vol.9 (12), p.e23104-e23104, Article e23104 |
---|---|
Hauptverfasser: | , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | In this paper, two leaking tubes were investigated among copper tubes injected with 200 and 400 ppm benzotriazole after 8 years of usage. The electrochemical tests were conducted in simulated pit-out and pit-in environments (i.e., regions outside and inside of the pit) to determine the effect of benzotriazole on the propagation of an existing pit. The electrochemical analysis results showed that 200 and 400 ppm benzotriazole exhibit relatively lower inhibition efficiency in an acidic simulated pit-in environment because of the difficulty of forming a protective film and the benzotriazole cationization. |
---|---|