Corrosion rate optimization of mild-steel under different cooling tower working parameters using Taguchi design
This study investigates the implementation of Taguchi design in the estimation of minimum corrosion rate of mild-steel in cooling tower that uses saline solution of different concentration. The experiments were set on the basis of Taguchi’s L16 orthogonal array. The runs were carried out under diffe...
Gespeichert in:
Veröffentlicht in: | Journal of Engineering 2020, Vol.26 (1), p.174-185 |
---|---|
Hauptverfasser: | , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | This study investigates the implementation of Taguchi design in the estimation of minimum corrosion rate of mild-steel in cooling tower that uses saline solution of different concentration. The experiments were set on the basis of Taguchi’s L16 orthogonal array. The runs were carried out under different condition such as inlet concentration of saline solution, temperature, and flowrate. The Signal-to- Noise ratio and ANOVA analysis were used to define the impact of cooling tower working conditions on the corrosion rate. A regression had been modelled and optimized to identify the optimum level for the working parameters that had been founded to be 13%NaCl, 35ᴼC, and 1 l/min. Also a confirmation run to establish the precision of the Taguchi design for optimization the corrosion rate in cooling tower with high reliability. The contour plot had been applied to understand how it can be in finding the relation between the corrosion rate and the working parameters of the cooling tower |
---|---|
ISSN: | 1726-4073 2520-3339 |
DOI: | 10.31026/j.eng.2020.01.13 |