Study on the lightning shielding characteristics of the crossover area of UHV/HV transmission lines

Due to space limitations of transmission corridors, ultrahigh voltage (UHV) lines inevitably cross over other lines. UHV lines in a crossover section have a lightning shielding effect similar to that of a lightning conductor of lower lines. While, whether a 500-kV line below a crossover section meet...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Energy reports 2022-08, Vol.8, p.806-814
Hauptverfasser: Deng, Yeqiang, Li, Jisheng, Pan, Hao, Wang, Yu, Chen, Xiaoyue, Gao, Lei, Wan, Baoquan, Liu, Jianben
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Due to space limitations of transmission corridors, ultrahigh voltage (UHV) lines inevitably cross over other lines. UHV lines in a crossover section have a lightning shielding effect similar to that of a lightning conductor of lower lines. While, whether a 500-kV line below a crossover section meets the lightning protection requirements is unknown. Therefore, a calculation method for the shielding failure trip rate of transmission lines in a crossover section in a three-dimensional space is proposed. The calculation of the shielding failure trip rate of the 500-kV line without a ground wire below the UHV line was performed. The results revealed that the shielding failure rate of the lower line was positively correlated with the length of the lower line and was negatively correlated with the crossing angle and length of the upper line. The maximum traversal lengths for a 500-kV line without a ground wire below a UHV AC or DC line were 200 m and 150 m, respectively. These findings provide a scientific basis for lightning protection design of ultra-UHV line crossing areas.
ISSN:2352-4847
2352-4847
DOI:10.1016/j.egyr.2022.02.214