Single-tuned passive filter (STPF) for mitigating harmonics in a 3-phase power system
Numerous integrals of the fundamental frequency are known as harmonics and can be found in power systems or electrical circuitry systems. Non-linear loads occasionally drain current or contains a varying impedance with each period of the AC voltage are often responsible for power system harmonics. T...
Gespeichert in:
Veröffentlicht in: | Scientific reports 2023-11, Vol.13 (1), p.20754-20754, Article 20754 |
---|---|
Hauptverfasser: | , , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Numerous integrals of the fundamental frequency are known as harmonics and can be found in power systems or electrical circuitry systems. Non-linear loads occasionally drain current or contains a varying impedance with each period of the AC voltage are often responsible for power system harmonics. This can result in system overheating, system losses, and equipment or system damage. In order to achieve the IEEE 519 power quality standard, filters are routinely employed to lower harmonic levels. In this work, we designed a single tuned passive filter (STPF) to minimize harmonics of sequence 5th, 7th, 11th, 13th, 17th, and 19th in a three (3) phase power system. The measurements were taken at the point of common coupling. To test the filter performance, the system and STPF were designed in MATLAB/Simulink, and the simulated results produced without and with STPF were compared. The
THD
I
was reduced from 14.93% down to 4.87% when STPF was connected which is within the IEEE 519-2022 standard; proving that the STPF was effective in decreasing the harmonics to the desired level. |
---|---|
ISSN: | 2045-2322 2045-2322 |
DOI: | 10.1038/s41598-023-47614-7 |