Research on pH control strategy for internal cooling water in generators with dissolved CO2

The core of generator internal cooling water treatment is to control the pH of the internal cooling water within the range of 8.0-9.0, to realize the control of copper wires corrosion through a slightly alkaline environment. It is quite important to monitor the pH of the internal cooling water in ge...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Gong ye shui chu li 2024-09, Vol.44 (9), p.193-198
Hauptverfasser: CHEN Jianliang, HAO Hongduo, KE Bo, WANG Lin, HUANG Wanqi, CHANG Hao
Format: Artikel
Sprache:chi
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The core of generator internal cooling water treatment is to control the pH of the internal cooling water within the range of 8.0-9.0, to realize the control of copper wires corrosion through a slightly alkaline environment. It is quite important to monitor the pH of the internal cooling water in generators. However, due to the low conductivity of the internal cooling water and the influence of factors such as liquid contact potential, flow potential, and pure water temperature compensation, it is difficult to accurately determine its pH using traditional pH electrodes, and it is very easy to dissolve CO2 in the internal cooling water. Therefore, conventional computational pH instruments are not suitable. A mathematical model was established for the relationship between pH, electrical conductivity, and hydrogen conductivity in internal cooling water of generator with dissolved CO2 and NH3 as alkalization agent, based on Kohlrausch’s law of ion independent movement. The accuracy of the model was verified throu
ISSN:1005-829X
DOI:10.19965/j.cnki.iwt.2023-1161