Impact of High PV Penetration on the Inter-Area Oscillations in the U.S. Eastern Interconnection

This study explores the impact of high-photovoltaic (PV) penetration on the inter-area oscillation modes of large-scale power grids. A series of dynamic models with various PV penetration levels are developed based on a detailed model representing the U.S. Eastern Interconnection (EI). Transient sim...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE access 2017, Vol.5, p.4361-4369
Hauptverfasser: Shutang You, Gefei Kou, Yong Liu, Xuemeng Zhang, Yi Cui, Till, Micah J., Wenxuan Yao, Yilu Liu
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This study explores the impact of high-photovoltaic (PV) penetration on the inter-area oscillation modes of large-scale power grids. A series of dynamic models with various PV penetration levels are developed based on a detailed model representing the U.S. Eastern Interconnection (EI). Transient simulations are performed to investigate the change of inter-area oscillation modes with PV penetration. The impact of PV control strategies and parameter settings on inter-area oscillations is studied. This paper finds that as PV increases, the damping of the dominant oscillation mode decreases monotonically. It is also observed that the mode shape varies with the PV control strategy and new oscillation modes may emerge under inappropriate parameter settings in PV plant controls.
ISSN:2169-3536
2169-3536
DOI:10.1109/ACCESS.2017.2682260