Comprehensive Analysis of LCL Filter Interfaced Cascaded H-Bridge Multilevel Inverter-Based DSTATCOM
Three-phase two-level voltage source converters are used for distribution static compensator (DSTATCOM) applications and can be replaced by a multilevel inverter. In this paper, an LCL filter interfaced cascaded H-bridge multilevel inverter-based (CHBMLI) DSTATCOM is simulated and its performance is...
Gespeichert in:
Veröffentlicht in: | Energies (Basel) 2017-03, Vol.10 (3), p.346 |
---|---|
Hauptverfasser: | , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Three-phase two-level voltage source converters are used for distribution static compensator (DSTATCOM) applications and can be replaced by a multilevel inverter. In this paper, an LCL filter interfaced cascaded H-bridge multilevel inverter-based (CHBMLI) DSTATCOM is simulated and its performance is analyzed considering the system parameters. The analysis considers factors including the switching frequency, modulation index, and filter parameters of a DSTATCOM system. The LCL filter design and analysis for the low switching frequency operation of CHBMLI is proposed in this paper. Phase shift pulse-width modulation is used for the generation of switching signals. The reference current is generated using synchronous reference frame theory (SRFT) for reactive power and harmonic compensations. The simulation model of the CHBMLI-based DSTATCOM system is developed in MATLAB Simulink. The results are demonstrated for a linear/non-linear load under unbalanced conditions, considering the voltage sag and swell in the system due to a disturbance in the load. |
---|---|
ISSN: | 1996-1073 1996-1073 |
DOI: | 10.3390/en10030346 |