Detection and Location of Earth Fault in MV Feeders Using Screen Earthing Current Measurements
The paper analyzes the utilization of cable screen currents for earth fault identification and location. Attention is paid on cable and mixed feeders—cable and overhead lines. The principle of operation is based on utilization of 3 criterion values: Ratio of cable screen earthing current and zero se...
Gespeichert in:
Veröffentlicht in: | Energies (Basel) 2020-03, Vol.13 (5), p.1293 |
---|---|
Hauptverfasser: | , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The paper analyzes the utilization of cable screen currents for earth fault identification and location. Attention is paid on cable and mixed feeders—cable and overhead lines. The principle of operation is based on utilization of 3 criterion values: Ratio of cable screen earthing current and zero sequence cable core current—RF110/15, phase shift between cable screen earthing current and zero sequence cable core current—α and cable screen admittance defined as a ratio of cable screen earthing current and zero sequence voltage—Y0cs. Earth fault location is possible thanks to discovered relation between RF110/15 and α, whereas Y0cs allows for reliable detection of earth faults. Detection and identification are very important because it allows to increase the reliability of supply—reduce downtime and number of consumers affected by the fault. The article presents a phase to ground fault current flow for different power system configurations. At the end solution, which improves location capabilities is proposed. The solution is analyzed in PSCAD software and verified by network experiment. |
---|---|
ISSN: | 1996-1073 1996-1073 |
DOI: | 10.3390/en13051293 |