A state‐space average model of a three‐level PV inverter for transient short‐circuit currents analysis

This paper presents a state‐space average model of a three‐level photovoltaic (PV) inverter to understand short‐circuit currents transient characteristics. Analytical solution of the model is also derived. The proposed model is validated with PV system controller hardware in‐loop (HIL) test method....

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IET Generation, Transmission & Distribution Transmission & Distribution, 2024-05, Vol.18 (9), p.1855-1870
Hauptverfasser: Yuan, Shuai, Wen, Bing, Zhang, Jian‐Ying, Li, Zhimin
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This paper presents a state‐space average model of a three‐level photovoltaic (PV) inverter to understand short‐circuit currents transient characteristics. Analytical solution of the model is also derived. The proposed model is validated with PV system controller hardware in‐loop (HIL) test method. The errors between simulation and HIL tests results under various conditions are evaluated, testifying the validity of the proposed model. With the model and analytical solution, the decaying time constants of sub‐transient and transient processes are derived, which shows that the time constants of a three‐level PV inverter are not fixed and they vary with voltage dips. The analytical expression of short‐circuit currents is also formulated. The findings from this study are essential to short‐circuit current calculations of a power grid with large‐scale PV plants, coordination of power system protections, and grid planning. 1. This paper presents a state‐space average model of a three‐level PV inverter to characterize the short‐circuit currents transient behaviours. 2. Analytical solution of a three‐level PV inverter state‐space average model is derived and short‐circuit currents are also formulated. 3. With the model and analytical solution, the decaying time constants of sub‐transient and transient processes are derived, which shows that the time constants of a three‐level PV inverter are not fixed and they vary with voltage dips.
ISSN:1751-8687
1751-8695
DOI:10.1049/gtd2.13163