Research on a capacitive particle analysis smoke detector

Smoke detectors face the challenges of increasing accuracy, sensitivity, and high reliability in complex use environments to ensure the timeliness, accuracy, and reliability of very early fire detection. The improvement and innovation of the principle and algorithm for smoke particle concentration d...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Scientific reports 2024-05, Vol.14 (1), p.11319-11319, Article 11319
Hauptverfasser: Wang, Boqiang, Zhao, Xuezeng, Zhang, Yiyong, Song, Zigang, Wang, Zhuogang
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Smoke detectors face the challenges of increasing accuracy, sensitivity, and high reliability in complex use environments to ensure the timeliness, accuracy, and reliability of very early fire detection. The improvement and innovation of the principle and algorithm for smoke particle concentration detection provide opportunities for improving the performance of the detector. This study represents a new refinement of the smoke concentration detection principle based on capacitive detection of cell structures, and detection signals are processed by a multiscale smoke particle concentration detection algorithm to calculate smoke concentration. Through experiments, it was found that the detector provides effective detection of smoke particle concentrations ranging from 0 to 10% obs/m; moreover, when the detection accuracy is greater than a certain number of parts per million (PPM), the sensitivity of the detector can reach the PPM level; furthermore, the detector can detect smoke particle concentrations higher than the PPM level accuracy even in an environment with a certain concentration of petroliferous and dust particles of different sizes.
ISSN:2045-2322
2045-2322
DOI:10.1038/s41598-024-62400-9