Cooperative Optimization of A Refrigeration System with A Water-Cooled Chiller and Air-Cooled Heat Pump by Coupling BPNN and PSO

Aiming at the issues of unreasonable cooperation schemes and inappropriate setting of parameters of the refrigeration system with multi-chiller plants, this paper presents a cooperative optimization method to improve the energy performance of the system composed of water-cooled chillers and air-cool...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Energies (Basel) 2022-10, Vol.15 (19), p.7077
Hauptverfasser: Deng, Qinli, Xu, Liangxin, Zhao, Tingfang, Hong, Xuexin, Shan, Xiaofang, Ren, Zhigang
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Aiming at the issues of unreasonable cooperation schemes and inappropriate setting of parameters of the refrigeration system with multi-chiller plants, this paper presents a cooperative optimization method to improve the energy performance of the system composed of water-cooled chillers and air-cooled heat pumps. The cooperative optimization process includes scheme optimization and parameter optimization. To content the dynamic cooling load, the working sequence of air-cooled heat pumps and water-cooled chillers with variable frequency chilled water pumps is first optimized. Based on the optimal scheme, a back-propagation neural network (BPNN) coupled with particle swarm optimization (PSO) is implemented to explore the preferred operating parameters of multiple chiller plants corresponding to the best coefficient of performance (COP). Compared with the performance of the initial operation module, the energy consumption of the water pump and fan decreases by over 50%, and the COP of the refrigeration system is improved by 16% (COP = 3.85) through the scheme operation. After parameter optimization, the total energy consumption is reduced by 21.7%, and COP is increased by 26.5% (COP = 4.20). Therefore, the proposed cooperative optimization method can provide useful operation guidance for the refrigeration system with multi-chiller plants.
ISSN:1996-1073
1996-1073
DOI:10.3390/en15197077