Fire resistance of ceramic-masonry sealing blocks using intumescent paint protection

The efficiency of surface protection of sealing masonry structures with intumescent ink was evaluated in relation to mechanical resistance and thermal insulation. Sixty ceramic sealing masonry blocks were used. The temperature of the face directly exposed to the flame was on average 25% lower for th...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Revista ALCONPAT 2020-04, Vol.10 (1), p.53-68
Hauptverfasser: Santos Sales, Carlos Alexandre, Gomes do Nascimento, Carlos Fernando, Marques da Silva, Thais, Marques Barreto, Lydia, Casado Lordsleem Júnior, Alberto, De Albuquerque Soares, Willames, Castro Borges, Pedro, Barreto Monteiro, Eliana Cristina
Format: Artikel
Sprache:eng ; por
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The efficiency of surface protection of sealing masonry structures with intumescent ink was evaluated in relation to mechanical resistance and thermal insulation. Sixty ceramic sealing masonry blocks were used. The temperature of the face directly exposed to the flame was on average 25% lower for the block with passive protection. The compressive strength of the blocks with passive protection was about 70% higher than the unprotected blocks, after 60 minutes of direct exposure to the flame. More than 70% of the blocks without passive protection and that were exposed to flame had compressive resistance of 1.35 MPa, while 100% of the blocks with protection had values 2.38 MPa, even after 60 minutes of exposure
ISSN:2007-6835
2007-6835
DOI:10.21041/ra.v10i1.417