An active damping control strategy for suppressing LCL resonant point migration for three-phase grid-tied inverter

LCL filters are extensively utilized in Grid-connected inverters due to their exceptional capability in suppressing high-frequency harmonics. The active damping method is commonly employed to mitigate the resonance peak of the LCL filter. However, this control strategy induces a shift in the natural...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Scientific reports 2024-10, Vol.14 (1), p.22911-17, Article 22911
Hauptverfasser: Chen, Dongdong, Zhang, Shengqi, Lin, Hongyi
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:LCL filters are extensively utilized in Grid-connected inverters due to their exceptional capability in suppressing high-frequency harmonics. The active damping method is commonly employed to mitigate the resonance peak of the LCL filter. However, this control strategy induces a shift in the natural resonance point. To address this issue, a novel active damping control strategy based on the principle of equivalent transformation is proposed in this paper, which not only effectively suppresses the resonance peak but also avoids deviation from the natural resonance point. Finally, experiments are carried out on a three-phase LCL Grid-connected inverter, and the experimental results show that the control strategy has good steady-state performance, dynamic response, and robustness under both rigid and ultra-weak network conditions.
ISSN:2045-2322
2045-2322
DOI:10.1038/s41598-024-73897-5