Preventive DC‐side decoupling: A system integrity protection scheme to limit the impact of DC faults in offshore multi‐terminal HVDC systems
To create synergies between offshore wind integration and operational flexibility, interconnecting HVDC links to multi‐terminal networks is highly desired. However, its technical realisation remains a major challenge: In particular, it is crucial to prevent DC faults from leading to an intolerable l...
Gespeichert in:
Veröffentlicht in: | IET generation, transmission & distribution transmission & distribution, 2024-12, Vol.18 (23), p.3801-3816 |
---|---|
Hauptverfasser: | , , , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | To create synergies between offshore wind integration and operational flexibility, interconnecting HVDC links to multi‐terminal networks is highly desired. However, its technical realisation remains a major challenge: In particular, it is crucial to prevent DC faults from leading to an intolerable loss of power infeed to the connected AC grids. To restrict this loss of power infeed, this paper proposes a concept for linear HVDC networks that is based on state‐of‐the‐art equipment only—that is, without dependence on DC circuit breakers. In this concept, the DC interconnection is preventively decoupled via DC high‐speed switches whenever the cumulative wind infeed exceeds the frequency containment reserve of the AC grid, but remains coupled at all other times. The decoupling is realised via controlling the coupling line current to zero through coordinated setpoint changes for the converters’ (VDC/P)‐droop controls. Both the decoupling sequence and the DC fault behaviour in decoupled state are validated via EMT simulations. In addition, limitations with regard to expandability are discussed. The proposed concept may not only limit the loss of infeed, but mitigates risks as a fall‐back level for more complex offshore (multi‐vendor) multi‐terminal HVDC topologies—and may thus accelerate their development at reasonable costs.
For the integration of offshore wind power, the interconnection of HVDC links towards multi‐terminal networks is highly desired, but considered technically challenging. The preventive DC‐side decoupling concept proposed in this paper enables multi‐terminal operation of offshore HVDC networks without the need for additional protection hardware â€″ that is, without dependency on DC circuit breakers. It can be interpreted as a system integrity protection scheme, and may as such simplify, de‐risk, and accelerate the first linear offshore HVDC‐side interconnections. |
---|---|