Multi DC coordinated transient overvoltage suppression strategy for high proportion new energy sending terminal area

Aiming at the transient overvoltage problem of high proportion new energy multi direct current (DC) transmission system caused by DC blocking fault, the interaction mechanism between multiple DC lines is analyzed firstly and the multi-outfeed voltage infection factor is introduced, which reveals the...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:电力工程技术 2023-01, Vol.42 (1), p.98-106
Hauptverfasser: ZHANG Qirui, XIN Chaoshan, LI Fengting, YIN Chunya, LIU Jiangshan, LI Yuan
Format: Artikel
Sprache:chi
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Aiming at the transient overvoltage problem of high proportion new energy multi direct current (DC) transmission system caused by DC blocking fault, the interaction mechanism between multiple DC lines is analyzed firstly and the multi-outfeed voltage infection factor is introduced, which reveals the fundamental reason of transient overvoltage of other sound DC near area alternating current (AC) systems caused by DC blocking. Secondly, based on the quantitative relationship between reactive power output of the synchronous condenser in different time scales and rectifier side commutation bus voltage and improved rectifier side control of DC system, the capacity of the synchronous condenser installed on the rectifier side bus is configured and the required investment capacity is reduced. Thirdly, based on the above strategy, integrating the reactive power regulation capability of the synchronous condenser and rectifier, a transient overvoltage suppression strategy with coordinated cooperation of multi DC and mul
ISSN:2096-3203
DOI:10.12158/j.2096-3203.2023.01.012