Energy-efficient ventilation control strategies for surgery rooms

Surgery room specific energy use is among the highest in the built environment due to stringent indoor environmental quality and infection control requirements. This study uses a calibrated energy model to evaluate the environmental and economic performance of a variety of ventilation control strate...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Science & technology for the built environment 2015-01, Vol.21 (2), p.228-237
Hauptverfasser: Cubi Montanya, Eduard, Salom Tormo, Jaume, Garrido Soriano, Nuria
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Surgery room specific energy use is among the highest in the built environment due to stringent indoor environmental quality and infection control requirements. This study uses a calibrated energy model to evaluate the environmental and economic performance of a variety of ventilation control strategies that reduce surgery room energy use while maintaining indoor environmental quality and infection control performance. The individual control strategies evaluated in this study are (1) temperature and relative humidity reset, (2) air recirculation, (3) airflow reset, and (4) particle concentration based airflow control. Combinations of these strategies are also evaluated. The best performing combinations of control strategies can reduce surgery room primary energy use, CO 2 emissions, and energy costs by up to 86% relative to the standard practice. Temperature and relative humidity reset is the strategy that offers the largest benefits. Particle concentration based airflow control shows modest results partly due to the conservative infection control performance target. Future research should define infection control performance thresholds during operation.
ISSN:2374-4731
2374-474X
2374-474X
DOI:10.1080/23744731.2014.992708