Studying the performance of evaporative cooler using pre-cooling water system

The big increase of the ambient temperature during the summer season leads to increase of energy consumption for air conditioning which in turn increases peak electrical study load. In this work, theoretical and experimental study are performed for hybrid system combined of evaporative air cooler an...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Thi-Qar University Journal for Engineering Sciences. 2018-06, Vol.9 (1), p.1-8
Hauptverfasser: Hammadi, Salman Hisham, Jabir, Adi Kazim
Format: Artikel
Sprache:eng
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The big increase of the ambient temperature during the summer season leads to increase of energy consumption for air conditioning which in turn increases peak electrical study load. In this work, theoretical and experimental study are performed for hybrid system combined of evaporative air cooler and refrigeration unit. The experimental rig is build and tested during the summer months. The theoretical model is performed based on heat and mass transfer for the hybrid system. The effect of may parameters are studied such as, water temperature, water and air mass flowrates and wetted pad thickness. The results show that the pre-cooling water temperature improves effectiveness by about (5-10%). The results of the present work are compared with results of other works and show a good agreement
ISSN:2664-5564
2664-5572
DOI:10.31663/utjes.v9i1.1