Improving the Power System safety in Hospitals by means of periodical SFRA tests on Medical Isolation Transformers
The paper has the main aim of demonstrating a possible use ofthe well consolidated monitoring SFRA (Sweep Frequency Response Analysis)technique for preventive maintenance procedure applied to isolation medical transformers operating in hospitals’ group...
Gespeichert in:
Veröffentlicht in: | RE&PQJ 2024-01, Vol.16 (3) |
---|---|
Hauptverfasser: | , , , , |
Format: | Artikel |
Sprache: | eng |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The paper has the main aim of demonstrating a possible use ofthe well consolidated monitoring SFRA (Sweep Frequency Response Analysis)technique for preventive maintenance procedure applied to isolation medical transformers operating in hospitals’ group 2 medical locations. In particular, a novel testing platform has been implemented that can perform the monitoring test on IT-M during normal periodical verification provided by specific standard.In the paper, some results of the practical application of such a platform to several transformers in currently in operation in various Italian hospitals have been reported. |
---|---|
ISSN: | 2172-038X 2172-038X |
DOI: | 10.24084/repqj18.300 |