Development of a Condensive Capacitor for Countermeasure of Harmonics and its Application to Customers Substation

Trouble due to harmonics rapidly increases after 1990. A ratio of troubled equipment caused by the harmonics shows a series reactor and a power capacitor account for 65% and 26%, respectively. A modified JIS recommends allowance 5th harmonic current of 55% in the series reactor, and standardize to a...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Denki Gakkai ronbunshi. B, Enerugi, denki kiki, denryoku 2001/12/01, Vol.121(12), pp.1800-1806
Hauptverfasser: Oku, Kiyoshi, Nakamura, Osamu
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Trouble due to harmonics rapidly increases after 1990. A ratio of troubled equipment caused by the harmonics shows a series reactor and a power capacitor account for 65% and 26%, respectively. A modified JIS recommends allowance 5th harmonic current of 55% in the series reactor, and standardize to a 6% series reactor for a capacitor. However, to install the capacitor with the 6% series reactor due to harmonic current is sometimes the temperature rise in observed. The authors clarify a combination of capacitor and reactor to reduce harmonic current efficiently. A Capacitor based on the combination is applied to customer substations of 6.6kV and 33kV. This paper describes the capacitor, which is named Tough Var, and test results at the substations.
ISSN:0385-4213
1348-8147
DOI:10.1541/ieejpes1990.121.12_1800