Synthetic Testing of Load Current Interruption in Medium Voltage Load Break Switches

To conduct the mainly active load current test duty according to IEC 62271-103, a directly powered test circuit and therefore a medium voltage connection or a power generator is needed. A newly developed synthetic test circuit allows to replicate the current as well as the full transient recovery vo...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Hauptverfasser: Bendig, M., Ksoll, M., Kalter, A., Schaak, M., Ermeler, K., Schnettler, A.
Format: Tagungsbericht
Sprache:eng
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:To conduct the mainly active load current test duty according to IEC 62271-103, a directly powered test circuit and therefore a medium voltage connection or a power generator is needed. A newly developed synthetic test circuit allows to replicate the current as well as the full transient recovery voltage (TRV) and the power frequent recovery voltage (RV) of the direct test circuit up to its crest value. It is dimensioned for voltage classes up to 52 kV and can be adapted to test currents between 630 A and 1250 A. The test circuit allows a detailed investigation of load break switches without costly high power sources and loads. Many parameters, like current and voltage steepness at current zero, as well as different parameters defining the TRV steepness can be varied individually.
ISSN:2336-2626
2336-2634
DOI:10.14311/ppt.2017.3.241