Fire-extinguishing performance and gas-phase pollution characteristics of different foam agents in extinguishing transformer oil pool fire

In this study, aqueous film-forming foam, fluoroprotein foam, and synthetic foam were applied to extinguish the transformer oil pool fires. The fire-extinguishing performance and burn-back resistance were investigated using a laboratory fire-extinguishing system. Moreover, the emission products were...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Journal of fire sciences 2022-11, Vol.40 (6), p.463-478
Hauptverfasser: Zhang, Jiaqing, Shang, Fengju, Zhou, Wencheng, Xiao, Fei, Cheng, Dengfeng
Format: Artikel
Sprache:eng
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:In this study, aqueous film-forming foam, fluoroprotein foam, and synthetic foam were applied to extinguish the transformer oil pool fires. The fire-extinguishing performance and burn-back resistance were investigated using a laboratory fire-extinguishing system. Moreover, the emission products were analyzed to evaluate the gas-phase pollution characteristics. Results show that aqueous film-forming foam presents the highest fire-extinguishing efficiency, while fluoroprotein foam has the best burn-back performance. Flue gas and gas chromatography–mass spectrometer analyses demonstrate that the use of fluoroprotein foam results in much higher CO emissions than other foams, and the pollutants are mainly from various hydrocarbons produced by incomplete combustion of transformer oil. Synthetic foam and aqueous film-forming foam lead to higher SO2 and NO emissions, and pollutants are mainly dominated by alcohols and ethers. Noteworthily, when using aqueous film-forming foam to extinguish oil pool fire, a persistent organic pollutant, perfluorooctanoic acid, is detected in the gas phase.
ISSN:0734-9041
1530-8049
DOI:10.1177/07349041221142509