Electric Power PSS With Ramp-Rejection
The object of this paper is to demonstrate the performance of a Ramp-Rejecting electric Power Prefilter (RRPP), which is a modification of the Conventional electric Power Prefilter (CPP) for a speed-PSS. The RRPP can markedly reduce the undesirable swings in generator voltage and reactive power outp...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on power systems 2020-11, Vol.35 (6), p.4495-4504 |
---|---|
Hauptverfasser: | , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The object of this paper is to demonstrate the performance of a Ramp-Rejecting electric Power Prefilter (RRPP), which is a modification of the Conventional electric Power Prefilter (CPP) for a speed-PSS. The RRPP can markedly reduce the undesirable swings in generator voltage and reactive power output due to ramping of turbine power. Like the Dual Input Prefilter (DIP) of the integral-of-accelerating-power (IAP) PSS the RRPP (i) significantly attenuates the torsional modes; and (ii) enhances modal damping. Significantly, the RRPP does not require an externally-estimated rotor-speed input signal - which is an important requirement of the DIP. For example, using generator terminal variables for the DIP it is difficult to accurately estimate a rotor-speed input that covers a wide range of operating conditions and modal frequencies. |
---|---|