Individual Load Model Parameter Estimation in Distribution Systems Using Load Switching Events

There currently exists a mature literature on modeling the aggregate load of a distribution feeder by making use of measurements at its feeder-head at substation. The primary application of such feeder-aggregated load models is in sub-transmission or transmission system analysis. However, there is a...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power systems 2019-11, Vol.34 (6), p.4652-4664
Hauptverfasser: Shahsavari, Alireza, Farajollahi, Mohammad, Mohsenian-Rad, Hamed
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:There currently exists a mature literature on modeling the aggregate load of a distribution feeder by making use of measurements at its feeder-head at substation. The primary application of such feeder-aggregated load models is in sub-transmission or transmission system analysis. However, there is a growing need in practice also to model each individual load across the feeder. If available, such individual load models have applications in power distribution system analysis, e.g., to better integrate distributed energy resources or to improve power quality and reliability. Motivated by this observation, in this paper, we propose a new method for individual load modeling in power distribution systems. It works by using the measurements only at the feeder-head. It takes an innovative approach to analyzing the load switching events across the distribution feeder itself, instead of or in addition to relying on upstream voltage events that are commonly used in feeder-aggregated load modeling. By tracking the downstream load switching events, the proposed method can make a robust estimation of the ZIP load model parameters for all individual loads. The proposed method is examined on small illustrative test-feeders as well as the IEEE 33-bus test system under various operating scenarios. The adverse impact of errors in measurements and system parameters are also investigated on the performance of the developed load modeling method.
ISSN:0885-8950
1558-0679
DOI:10.1109/TPWRS.2019.2919901