The Use of Partial Discharges as an Online Monitoring System for Underground Cable Joints

With their vast amount of joints, underground cable systems are expensive to maintain; therefore, measurement equipment must be cost-effective. This study proposes the long-term placement of partial-discharge (PD) monitoring units at cable joints. The unit consists of a peak detect circuit and a dig...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2011-07, Vol.26 (3), p.1585-1591
Hauptverfasser: WU, Ruay-Nan, CHANG, Chien-Kuo
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:With their vast amount of joints, underground cable systems are expensive to maintain; therefore, measurement equipment must be cost-effective. This study proposes the long-term placement of partial-discharge (PD) monitoring units at cable joints. The unit consists of a peak detect circuit and a digital signal processor for acquiring and converting the sensors' PD signals into discharge sequence data, whose data are then provided to a remote computer for analysis and display of the condition of the cable joint. Finally, a cable joint with artificial defects was tested by accelerated aging tests to verify the performance of the equipment. Two characteristics, namely, the average discharge quantity (Q ave ) and the discharge phase region, are proposed and plotted against each other to render an evolution locus, which reveals a shape of an upside-down letter N. The locus allows a judgment to be made on the state of the insulation in the cable joint. These results further justify work to further develop the method as an online cable monitoring system.
ISSN:0885-8977
1937-4208
DOI:10.1109/TPWRD.2011.2124474