RTDS Environment Development of Ultra-High-Voltage Power System and Relay Protection Test

The increased interest in using ultra-high-voltage (UHV) transmissions has stimulated the research on UHV operation characteristic and correlative relay protections. Since the operational experience in UHV system is limited, there is a need to model UHV transmission systems and test the performance...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2008-04, Vol.23 (2), p.618-623
Hauptverfasser: Bin Wang, Xinzhou Dong, Zhiqian Bo, Perks, A.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The increased interest in using ultra-high-voltage (UHV) transmissions has stimulated the research on UHV operation characteristic and correlative relay protections. Since the operational experience in UHV system is limited, there is a need to model UHV transmission systems and test the performance of traditional protection devices already in use on high-voltage and extra-high-voltage systems. This paper presents the development of a test environment based on a real-time digital simulator of a UHV power system model and the results of testing a distance relay using the model. It reveals that the protective zone is enlarged in the UHV system with shunt reactor compensation and is reduced without the compensation. To resolve these issues further investigation is needed and ways of resolving them, including the development of new algorithms, should be examined.
ISSN:0885-8977
1937-4208
DOI:10.1109/TPWRD.2008.915818