Thermal problems caused by harmonic frequency leakage fluxes in three-phase, three-winding converter transformers
Harmonic frequency leakage flux can be a limiting factor in three-phase, three-winding HVDC converter transformers. Investigation of a three-phase, three-winding 240-MVA converter transformer failure indicated the failure was caused by harmonic fluxes. Calculations indicated that the magnitudes of t...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on power delivery 2004-01, Vol.19 (1), p.208-213 |
---|---|
Hauptverfasser: | , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Harmonic frequency leakage flux can be a limiting factor in three-phase, three-winding HVDC converter transformers. Investigation of a three-phase, three-winding 240-MVA converter transformer failure indicated the failure was caused by harmonic fluxes. Calculations indicated that the magnitudes of these harmonic fluxes to be approximately 45% of the power frequency leakage flux for the transformer, and are little affected by the transformer impedance or the converter firing angle. A study of the failed transformer loading during its life was made and a calculation made of the hot spot temperature considering various insulation half-life factors. Based on published information on insulation half-life factors it was estimated that at full load the hot spot temperature of the transformer was about 159/spl deg/C. From examination of the insulation in the hot spot area, this estimate of hot spot temperature was considered reasonable. |
---|---|
ISSN: | 0885-8977 1937-4208 |
DOI: | 10.1109/TPWRD.2003.820223 |