A General Design Procedure for Multi-Parallel Modular Grid-Tied Inverters System to Prevent Common and Interactive Instability
Based on the equivalent circuit model, the interactions of multi-parallel modular grid-tied inverters and their coupling effect with grid impedance are analyzed in this letter. The analysis shows that interactive instability could happen in the inverter system even when identical inverters have been...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on power electronics 2019-07, Vol.34 (7), p.6025-6030 |
---|---|
Hauptverfasser: | , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Based on the equivalent circuit model, the interactions of multi-parallel modular grid-tied inverters and their coupling effect with grid impedance are analyzed in this letter. The analysis shows that interactive instability could happen in the inverter system even when identical inverters have been used. However, if the control and circuit parameters are designed systematically, the system can be exempted from both common and interactive instability. The outcome of this research provides a practical general design paradigm for modular grid-tied inverters with inductor-capacitor-inductor ( LCL ) filters which can be used in the parallel operation with unknown number of modules. Experimental results are provided for verification. |
---|---|
ISSN: | 0885-8993 1941-0107 |
DOI: | 10.1109/TPEL.2019.2890842 |