A comparative analysis of multiloop voltage regulation strategies for single and three-phase UPS systems

Most of the many reported control algorithms for uninterruptible power supplies (UPSs) use either filter inductor or filter capacitor currents as feedback variables to regulate the output voltage. This paper explores the fundamental performance issues associated with the use of these quantities as f...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power electronics 2003-09, Vol.18 (5), p.1176-1185
Hauptverfasser: Poh Chiang Loh, Newman, M.J., Zmood, D.N., Holmes, D.G.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Most of the many reported control algorithms for uninterruptible power supplies (UPSs) use either filter inductor or filter capacitor currents as feedback variables to regulate the output voltage. This paper explores the fundamental performance issues associated with the use of these quantities as feedback variables, with a view to determining their contribution to the transient system response and output harmonic compensation in any particular situation. A proportional plus resonant (P+resonant) compensator is then added into the outer voltage regulation loop to achieve zero steady error, to develop a high performance UPS control algorithm, which is applicable to both single-phase and three-phase systems. Theory, simulation, and experimental results are presented in the paper.
ISSN:0885-8993
1941-0107
DOI:10.1109/TPEL.2003.816199