Frequency-Dependent Multi-Conductor Transmission Line Model for Shielded Power Cables Considering Geometrical Dissymmetry
In this paper, a broadband equivalent node-to-node admittance functions (NAFs) model for shielded power cables are presented aiming at the direct time-domain simulation. The finite-element method is employed to obtain the frequency-dependent per-unit-length resistances, self- and mutual-inductances,...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on magnetics 2018-03, Vol.54 (3), p.1-4 |
---|---|
Hauptverfasser: | , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | In this paper, a broadband equivalent node-to-node admittance functions (NAFs) model for shielded power cables are presented aiming at the direct time-domain simulation. The finite-element method is employed to obtain the frequency-dependent per-unit-length resistances, self- and mutual-inductances, and the self- and mutual-capacitances of the power cables. The matrix rational approximations are then applied to obtain the rational model (in pole-residue form) of the terminal admittance matrix of the multi-conductor transmission line (MTL) model. Next, the numerical stability of the rational model is guaranteed by the terminal (port) passivity enforcement technique. The circuit representation of the equivalent NAFs of the full cable with the length of interest can be synthesized based on the pole-residue description. It is validated by comparing the frequency response with the one computed by applying the original MTL model. |
---|---|
ISSN: | 0018-9464 1941-0069 |
DOI: | 10.1109/TMAG.2017.2751958 |