Evaluation of Delays Induced by Profibus PA Networks
The delays associated with the use of Profibus process automation (PA) networks within control loops are investigated in this paper. A SMAR IF303 device, a SMAR FI303 device, a DeltaV distributed control system, and a Siemens DP/PA link are used to implement a Profibus-PAnetwork-based test loop. Bot...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on instrumentation and measurement 2011-08, Vol.60 (8), p.2910-2917 |
---|---|
Hauptverfasser: | , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The delays associated with the use of Profibus process automation (PA) networks within control loops are investigated in this paper. A SMAR IF303 device, a SMAR FI303 device, a DeltaV distributed control system, and a Siemens DP/PA link are used to implement a Profibus-PAnetwork-based test loop. Both analysis and experiments are performed on the test loop. Loop-back delay models are developed and then validated against experimental results. Suggestions to potentially reduce Profibus-PA-network-induced delays are provided. A comparison between the estimated and the measured loop-back time demonstrates the accuracy of the delay models. Furthermore, the Profibus-PA-network-induced delays are compared against the delays induced by an equivalent Foundation Fieldbus H1 network with either hybrid or control-in-the-field architecture. |
---|---|
ISSN: | 0018-9456 1557-9662 |
DOI: | 10.1109/TIM.2011.2119070 |