Two-Degree-of-Freedom Current Controller to Mitigate Current Imbalance for Grid-Connected Inverters

This article proposes a current controller to mitigate current imbalance in grid-connected inverters. The proposed method avoids transforming unbalanced currents into their positive and negative sequence components. As a result, the number of current controllers is only two in d-q synchronous refere...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on industrial electronics (1982) 2024-10, Vol.71 (10), p.11766-11774
Hauptverfasser: Budiwicaksana, Lukas Antonio, Lee, Dong-Choon
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This article proposes a current controller to mitigate current imbalance in grid-connected inverters. The proposed method avoids transforming unbalanced currents into their positive and negative sequence components. As a result, the number of current controllers is only two in d-q synchronous reference frame. At the same time, it can also eliminate the current harmonics effectively. Imbalance and harmonics are regarded as disturbance, which guarantee the mitigation to have no effects on the current transient response. In other words, the controller has two-degree-of-freedom capability. Experimental results verify that the current unbalance factor and total harmonic distortion can be reduced from 42.6% to 0.2% and from 14.2% to 1.6%, respectively, without causing transient overshoot and oscillations. It is also shown that the proposed controller has 8.29 μ s shorter execution time than the conventional one.
ISSN:0278-0046
1557-9948
DOI:10.1109/TIE.2024.3360634