Harmonic Impact on Distribution Transformer No-Load Loss

The losses in European Union distribution transformers are estimated at about 33 TW ·h/year, whereas reactive power and harmonic losses add a further 5 TW ·h/year. The reduction of distribution transformer no-load loss is particularly important as the ratio of no-load to load losses is nearly three....

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on industrial electronics (1982) 2010-01, Vol.57 (1), p.193-200
Hauptverfasser: Kefalas, T.D., Kladas, A.G.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The losses in European Union distribution transformers are estimated at about 33 TW ·h/year, whereas reactive power and harmonic losses add a further 5 TW ·h/year. The reduction of distribution transformer no-load loss is particularly important as the ratio of no-load to load losses is nearly three. In this paper, the no-load operation of wound-core transformers under sinusoidal and distorted supply-voltage conditions is investigated. For that purpose, a 2-D nonlinear transient finite-element analysis taking into account hysteresis has been developed. The hysteresis model is based on a modified Jiles-Atherton representation, and the proposed analysis is compared to experimental data.
ISSN:0278-0046
1557-9948
DOI:10.1109/TIE.2009.2030207