Fall of Potential Measurement of the Earth Resistance in Urban Environments: Accuracy Evaluation

Both Standards EN 50522 and IEEE 81 propose the fall of potential method (FPM) to carry out the measurement of the resistance to earth (R_{\text{ES}}) of an earthing system (ES). However, in urban areas, the recommended distances between the ES and auxiliary electrodes are not easy to respect, due t...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on industry applications 2019-05, Vol.55 (3), p.2337-2346
Hauptverfasser: Colella, Pietro, Pons, Enrico, Tommasini, Riccardo, Silvestre, Maria Luisa Di, Sanseverino, Eleonora Riva, Zizzo, Gaetano
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Both Standards EN 50522 and IEEE 81 propose the fall of potential method (FPM) to carry out the measurement of the resistance to earth (R_{\text{ES}}) of an earthing system (ES). However, in urban areas, the recommended distances between the ES and auxiliary electrodes are not easy to respect, due to the presence of buildings and tarmac. Furthermore, unknown buried metallic parts and interconnections among ESs could modify the earth potential profile of the area, affecting the measurement results. In this paper, the key-issues that influence the measured R_{\text{ES}} when the FPM is used in an urban environment are presented. A parametric analysis, carried out with Comsol Multiphysics, quantifies the errors due to wrong positioning of the auxiliary electrodes and due to the presence of interconnected ESs in the proximity of the ES under test. In addition, a real case of field measurement is described, emphasizing the main aspects that could compromise the results. Finally, practical suggestions to reduce errors are provided.
ISSN:0093-9994
1939-9367