Medium-Voltage Switching Transient-Induced Potential Transformer Failures: Prediction, Measurement, and Practical Solutions
During commissioning of a large data center, while switching medium-voltage circuit breakers without any appreciable load, several potential transformers failed catastrophically. A detailed investigation, including a computer simulation, was performed. Ferroresonance produced by switching transients...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on industry applications 2013-07, Vol.49 (4), p.1726-1737 |
---|---|
Hauptverfasser: | , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | During commissioning of a large data center, while switching medium-voltage circuit breakers without any appreciable load, several potential transformers failed catastrophically. A detailed investigation, including a computer simulation, was performed. Ferroresonance produced by switching transients associated with opening and closing the vacuum breakers was determined to be the cause. The analysis also determined that the close-coupled power transformers were also in jeopardy. Field inspections involving grounding improvements coupled with solution simulations were made. High-speed switching transient measurements were performed to verify the analysis and the surge protective device solution (arresters and snubbers). This paper walks the reader through problem recognition, simulation, field measurements, and solution implementation. Special focus will be made on the field measurement verification. |
---|---|