The Measured Energy Savings from Two Lighting Control Strategies

The energy-saving benefits of two lighting control strategies -scheduling and daylighting-were investigated at demonstration sites in two large commercial buildings. A continuously dimmable lighting control system was installed at the Pacific Gas and Electric Company Building in San Francisco, and a...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE Trans. Ind. Appl.; (United States) 1984-09, Vol.IA-20 (5), p.1189-1197
Hauptverfasser: Ribinstein, Francis M., Karayel, Mahmut
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The energy-saving benefits of two lighting control strategies -scheduling and daylighting-were investigated at demonstration sites in two large commercial buildings. A continuously dimmable lighting control system was installed at the Pacific Gas and Electric Company Building in San Francisco, and an on/off switching system was installed at the World Trade Center in New York City. By automatically scheduling the operation of the lighting systems to conform with occupancy patterns, lighting energy consumption was reduced 10-40 percent. Several scheduling techniques were investigated, and the influence of switching the zone size on energy savings was examined. Using photoelectrically controlled lighting systems, which switch or dim lighting in accordance with available daylight, the energy consumed for lighting in daylit areas was reduced to 25-35 percent. The influence of clear and overcast conditions on the energy savings associated with daylight-linked controls is discussed.
ISSN:0093-9994
1939-9367
DOI:10.1109/TIA.1984.4504582