Insulator Pollution Performance at High Altitude: Major Trends

A survey of the data available from the literature was conducted in order to assess major trends in insulator performance with altitude. The literature comprised tests on individual insulator strings both under natural and artificial conditions along with actual live-in performance. The major trends...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE power engineering review 1989-04, Vol.9 (4), p.108-108
1. Verfasser: Mercure, Hubert P.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:A survey of the data available from the literature was conducted in order to assess major trends in insulator performance with altitude. The literature comprised tests on individual insulator strings both under natural and artificial conditions along with actual live-in performance. The major trends reported here suggest a pressure dependence (p/po)0.35 for DC and (p/po)0.5 for AC, of V50 for standard polluted insulators at altitudes lower than about 4 km (p ~ 0.6 atm). These pressure dependences impose a derating of the relative performance of leakage path length or flashover voltage with altitude, namely 6%/ km for AC, 5%/ km for positive DC and 4%/ km for negative DC applied voltages. Dielectric breakdown, in contrast, imposes a 10.5%/ km degradation of insulating air gaps with altitude.
ISSN:0272-1724
1558-1705
DOI:10.1109/MPER.1989.4310648