Separation of core losses in distribution transformers using experimental methods

The separation of eddy current and hysteresis losses in transformer cores is obtained using the two-temperatures and the two-frequency methods. Loss calculations for six ratings using the voltage test waveform ratio are included to compare and analyze results. A brief description of the test methodo...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Canadian journal of electrical and computer engineering 2010-01, Vol.35 (1), p.33-39
Hauptverfasser: Olivares-Galvan, J C, Escarela-Perez, R, de Leon, Francisco, Campero-Littlewood, E, Cruz, C Aviles
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The separation of eddy current and hysteresis losses in transformer cores is obtained using the two-temperatures and the two-frequency methods. Loss calculations for six ratings using the voltage test waveform ratio are included to compare and analyze results. A brief description of the test methodologies, that are easy to apply, is given. An example of the application of the methodologies, the obtained measurements and obtained results are included. In some cases, the results show that eddy current losses for the analyzed ratings are greater than 60% of no-load losses. Results include the impact of no-load losses in total owning cost of transformers.
ISSN:0840-8688
2694-1783