Characteristics of transformer exciting-current during geomagnetic disturbances
An efficient method allowing the transformer flux offset and exciting-current waveform to be determined for combined AC and geomagnetically induced current (GIC) excitation, without lengthy time-domain simulations, is described. This iterative approach solves for the equilibrium saturation condition...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on power delivery 1991-10, Vol.6 (4), p.1707-1714 |
---|---|
Hauptverfasser: | , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | An efficient method allowing the transformer flux offset and exciting-current waveform to be determined for combined AC and geomagnetically induced current (GIC) excitation, without lengthy time-domain simulations, is described. This iterative approach solves for the equilibrium saturation condition using lumped-parameter nonlinear magnetic-circuit models. In addition to investigating single-phase transformer performance, the authors examine the performance of certain three-phase transformer types for which GIC results in phase imbalance.< > |
---|---|
ISSN: | 0885-8977 1937-4208 |