Characteristics of transformer exciting-current during geomagnetic disturbances

An efficient method allowing the transformer flux offset and exciting-current waveform to be determined for combined AC and geomagnetically induced current (GIC) excitation, without lengthy time-domain simulations, is described. This iterative approach solves for the equilibrium saturation condition...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 1991-10, Vol.6 (4), p.1707-1714
Hauptverfasser: Walling, R.A., Khan, A.N.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:An efficient method allowing the transformer flux offset and exciting-current waveform to be determined for combined AC and geomagnetically induced current (GIC) excitation, without lengthy time-domain simulations, is described. This iterative approach solves for the equilibrium saturation condition using lumped-parameter nonlinear magnetic-circuit models. In addition to investigating single-phase transformer performance, the authors examine the performance of certain three-phase transformer types for which GIC results in phase imbalance.< >
ISSN:0885-8977
1937-4208